Choosing a Shielded Door: Strengthen the Room's Weakest Link
The door is the most common cause of lost performance in shielded rooms. We cover door types and why maintenance matters.
The only way to know whether a shielded room really works is to measure it. The measurement method step by step.
There is often a gap between a shielded room's performance on paper and its real performance. Panel quality, workmanship at the joints, door adjustment and penetrations added later all directly affect how much the room attenuates a signal. That is why the only reliable way to show that a shielded room delivers the required performance is a measurement made with a standard method.
In this article we explain how shielding effectiveness is measured, at which frequencies and at which points readings are taken, what standards such as EN 50147-1 and IEEE 299 define, how a measurement report should be read and how often the measurement should be repeated.
A shielding effectiveness measurement is essentially a comparison. First, a transmitting antenna and a receiving antenna are placed at a set distance with nothing between them, and the signal level at the receiver is recorded. This is the reference measurement. The transmitter is then placed outside the room and the receiver inside, and the measurement is repeated at the same distance. The difference between the two measurements shows by how many decibels the room attenuates the signal at that frequency.
The accuracy of the measurement depends on the dynamic range of the measurement system. If a dynamic range larger than the shielding value to be measured cannot be achieved, the real performance of the room cannot be measured; only the limit of the measurement system is seen. That is why powerful transmitters, low-noise receivers and short, high-quality cables are used when measuring high-performance rooms.
Because shielding effectiveness varies with frequency, the measurement is made at more than one frequency. At low frequencies, roughly between 9 kHz and a few MHz, magnetic field shielding is measured using loop antennas. This is the region where thin shields are weakest, and it is especially important in applications that need protection against magnetic fields.
At higher frequencies the measurement is made with dipole, biconical, log-periodic or horn antennas. Standards generally recommend choosing a few representative frequencies from each band. The frequencies to be measured and the acceptance values at each frequency should be defined in advance in the contract or specification; otherwise disagreements about which frequencies to measure may arise at handover.
The places in a shielded room where leakage is most likely are well known, and the measurement focuses on these points. Door edges, ventilation filters, cable and pipe penetrations, filter panels and panel joints are the main measurement points. Measurements made in the middle of walls usually give high values and do not reflect the room's real performance.
During the measurement, the transmitting antenna is placed opposite the point being measured, at the distance defined by the standard. On long joints such as doors, the measurement is repeated at several points. In some projects, a near-field scan is also carried out to pinpoint the location of a leak; this scan is part of troubleshooting, not of the reported measurement.
The most widely used standard in Europe is EN 50147-1. It was developed for measuring the shielding effectiveness of anechoic chambers, but is also widely applied to general shielded rooms. IEEE 299, of US origin, defines a more comprehensive method for shielded enclosures and covers 9 kHz to 18 GHz. Both standards are accepted in international projects.
In military projects, MIL-STD-285 may sometimes still be requested. Although this standard has been officially cancelled, it continues to appear in older specifications and in the technical documents of some organisations. Which standard applies, the measurement points and the acceptance limits should be written clearly in the contract. We have collected our advice on preparing specifications in our article how to write a shielded room specification.
For an accurate measurement, the room must be in its final working condition. All filters, penetrations and doors must be installed, door adjustments made and the room cleaned. No other work should take place in the room during the measurement, and the door should be opened and closed only by the measurement team.
Valid calibration of the measurement equipment is essential for the reliability of the values in the report. Marking the measurement points on the room plan in advance also makes the measurement quick and complete. If an independent body is to attend the acceptance measurement, this should be planned when the measurement date is set.
The measurement report shows the attenuation obtained at each frequency and each measurement point. The most important value in the report is the lowest, not the average, because the real performance of the room is that of its weakest point. For example, if 100 dB is measured at all points but 70 dB at a door corner, the room's performance at that frequency is 70 dB.
When comparing the values in a report, attention should be paid to the frequency range and the measurement method. Measurements made with different standards can give different results for the same room. We explain what dB values mean in our article what is dB, and what to watch out for at handover in our article on preparing for the acceptance test.
Shielding performance can decrease over time. Door gaskets wear, connections loosen, filters age and new penetrations are added to the room later. Most of these changes cannot be seen and only come to light through measurement. Periodic measurement of shielded rooms is therefore recommended.
Most organisations prefer to measure once a year; for heavily used or security-critical rooms this can be more frequent. When a major refurbishment, a new penetration or a door replacement takes place, an additional measurement should be made without waiting for the periodic one. For our measurement service, see our shielding measurement page.
The room should be in its final working condition, but no work should take place inside during the measurement. Items blocking access to measurement points can be removed temporarily.
Yes. For the values in the report to be reliable, the equipment used must have valid calibration.
Most organisations prefer once a year. More frequent measurement is recommended for heavily used or critical rooms, and an additional measurement after refurbishment.
Both measure shielding effectiveness, but their measurement setups, frequency bands and reporting details differ. Which one is used should be stated in the contract.
It depends on the size of the room and the number of measurement points and frequencies. A medium-sized room is usually measured within one working day.
The location of the leak is found with a near-field scan, the gasket, connection or filter mounting is usually corrected and the measurement is repeated at the relevant points.
Related Solutions
Your free site survey and quote will be ready within 24 hours.
The door is the most common cause of lost performance in shielded rooms. We cover door types and why maintenance matters.
Low-frequency magnetic fields cannot be stopped by ordinary shielding. We explain how magnetic shielding is done.
CISPR 25 testing, which makes sure in-vehicle electronics don't disturb the radio, GPS and other receivers, and the chamber it requires.