Magnetic Shielding: Flickering Screens in Offices Near Transformers

Low-frequency magnetic fields cannot be stopped by ordinary shielding. We explain how magnetic shielding is done.

In an office right next to a transformer room, monitors flicker, a sensitive laboratory instrument gives unexplained measurement errors, or employees ask whether the field they are constantly exposed to affects their health. In most of these cases the source is the same: transformers, busbars and cables carrying high currents produce a strong magnetic field at the 50 Hz mains frequency, and this field passes through walls almost without being weakened.

In this article we explain why low-frequency magnetic fields cannot be stopped by familiar shielding methods, which levels cause problems for which equipment, what can be done at the source and in the room to reduce the field, and how a magnetic shielding project is run from measurement to verification.

Where Does the Problem Come From?

When current flows through a conductor, a magnetic field forms around it, and the strength of this field is proportional to the current. Transformer substations, main distribution boards, busbar trunking and heavy power cables in buildings carry hundreds or even thousands of amperes, so they leave a noticeable field nearby. In a typical office the 50 Hz magnetic field is usually below 1 µT, while at the foot of a wall adjoining a transformer room it can rise from a few µT to tens of µT.

The field strength depends not only on the current but also on how the current is distributed. When the conductors of the three phases are placed close together and balanced, their fields largely cancel each other and fall off quickly with distance. In contrast, unbalanced currents returning through the neutral or the earthing system, wiring faults or cables whose phases run along separate routes produce fields that weaken much more slowly with distance. This is why a large part of the field people complain about comes not from the transformer itself but from the cabling around it.

Why Conventional Shielding Is Not Enough

Shielding against radio frequencies relies on eddy currents forming on a conductive metal surface. At high frequencies these currents cancel the incoming wave within a depth of a few micrometres, and thin copper or galvanised sheet is enough. At a very low frequency such as 50 Hz, however, this depth rises to the order of millimetres. A thin RF shield barely notices a low-frequency magnetic field; the field passes through the shield and reaches the room.

So no matter how good a shielded room's RF performance is, it will not stop the magnetic field of the transformer next door on its own. To deal with low-frequency magnetic fields, either the direction of the field must be changed with materials of high magnetic permeability, or eddy currents opposing the field must be created with sufficiently thick, conductive plates. Which method is chosen depends on the strength and direction of the field and the size of the area to be protected.

Which Level Is a Problem for Whom?

Two separate questions need to be distinguished here: human health and equipment operation. The ICNIRP 2010 guideline, used as an international reference for human exposure, recommends a reference level at 50 Hz of 200 µT for the general public and 1 mT for occupational exposure. Values measured in offices near transformer rooms are usually far below these limits. We cover health limits in detail in our article on ICNIRP limits.

For equipment the picture is different, because some devices are affected by fields hundreds of times below health limits. Electron microscopes, MRI and EEG systems, sensitive magnetic sensors and some audio systems can show image distortion, measurement errors or hum in a field of just a few µT. Manufacturers of these devices often ask for sub-µT values at the installation site. The immunity of information technology equipment is tested under IEC 61000-4-8 at levels of 1, 3, 10, 30 and 100 A/m; 1 A/m corresponds to about 1.26 µT.

What Can Be Done at the Source First?

Before moving to shielding, the possibility of reducing the field at its source should always be evaluated, because it is often more economical. If measurement shows that most of the field comes from unbalanced currents or cable routing, corrections to the installation can solve much of the problem instead of shielding. These corrections also improve the general quality of the electrical installation and often reduce other problems such as stray currents.

  • Running phase conductors and neutral along the same route, close together and bundled, lets the fields cancel each other.
  • Finding and correcting faulty connections between neutral and protective earth reduces stray currents circulating in the building and the field they produce.
  • Changing phase sequence in busbar trunking or moving cable trays away from the room to be protected lowers the field quickly with distance.
  • In new projects where the transformer or switchboard location can still change, planning sensitive rooms away from these sources is the most certain solution.

Whether these measures are enough is decided by measuring again after they are applied. If the remaining field is still above the target, shielding is designed for the residual field, which usually allows a thinner and cheaper solution.

How Is Magnetic Shielding Done?

When what can be done at the source is not enough, the room or area is shielded. The most common method is to route the field around the protected area using materials with high magnetic permeability. These materials offer field lines an easier path through themselves and so reduce the field entering the room. Grain-oriented electrical steel offers an economical solution on large surfaces, while mu-metal, a nickel-iron alloy, performs much better at low field levels; we explain how these materials work in our article on magnetic shielding with mu-metal.

The second approach is conductive shielding with aluminium or copper plates of sufficient thickness. These plates generate eddy currents that oppose the field itself and are particularly effective at high field strengths over large surfaces. In practice the two methods are often used together: layered panels are applied to the floor, walls or ceiling, joints are overlapped and continuity is maintained at corners. For very sensitive equipment such as electron microscopes, active compensation systems that measure the field with a sensor and produce a counter-field with coils can be used in addition to passive shielding.

Measurement, Design and Verification

Every magnetic shielding project starts with measurement. The room is scanned in a grid with a three-axis low-frequency magnetic field meter, and the strength, direction and variation of the field relative to the source are mapped. Because the load changes during the day, it is important to record over a period that ideally covers the busiest hours. We describe how the measurement is done in detail in our article on magnetic field measurement.

Measurement results and the target value are evaluated together to decide the material type, thickness, number of layers and surfaces to be treated. The target value comes from the manufacturer specification of the equipment to be protected or from an acceptance criterion set by the user. After installation, measurements are repeated at the same points and the before and after values are compared in a report. This makes the effect of the investment visible and immediately reveals any area that is still lacking.

Common Application Examples

The scenario we see most often is an office, meeting room or control room above or next to a transformer room. In these cases it is usually enough to cover only the floor and wall facing the transformer room; there is no need to enclose the whole room. Another common application is wrapping the trunking itself with magnetic material in corridors where busbar trunking or high-current cable trays pass. Each case is different, and measurement shows which surfaces really need treatment.

MRI and imaging rooms in hospitals, electron microscope and precision measurement laboratories at universities, and areas close to high-current distribution lines in data centres are other places where magnetic shielding is often applied. For systems that measure brain activity, such as MEG, multi-layer special magnetically shielded rooms are built; we cover this in our article on MEG rooms and magnetic shielding. For our solutions for energy infrastructure, see our energy sector page.

Frequently Asked Questions

Is the magnetic field near a transformer harmful to health?

Values measured in offices near transformer rooms are usually well below the 200 µT reference level recommended for the general public by the ICNIRP 2010 guideline. Still, having a measurement done is the best step to reassure employees and detect any possible problem.

Does a normal shielded room stop the transformer field?

No. Thin metal surfaces that are sufficient for RF shielding barely weaken low-frequency magnetic fields such as 50 Hz. This requires separate magnetic shielding with high-permeability magnetic materials or thick conductive plates.

How long does magnetic shielding take?

Depending on the size of the area and the number of surfaces to be treated, it can take from a few days to a few weeks. In most office applications, the working routine is affected only for a short time.

Is improvement guaranteed after shielding?

The target value is set at the start of the project together with the measurement. After installation, measurements are repeated at the same points and the results are reported in comparison with the previous values.

Can changes be made at the transformer instead of shielding?

Sometimes measures at the source, such as changing cable routing or eliminating stray currents, can be more economical than shielding. The measurement also shows whether this option is feasible.

Should mu-metal or electrical steel be used?

On large surfaces and at medium field levels, electrical steel offers a more economical solution. In sensitive equipment areas where very low target values are required, mu-metal or multi-layer designs are preferred. The choice is made according to the measurement results and the target value.