As dependence on electronic systems grows, so does the impact of events that can disable them in an instant. An electromagnetic pulse (EMP) is a high-intensity electromagnetic field that appears in a very short time and can cause permanent damage to electronic devices over a wide area. For facilities such as command centres, critical data centres and energy infrastructure, this risk is a direct part of business continuity.
In this article we explain what EMP and HEMP are, by which paths the pulse reaches systems, how protection is built through shielding and line entries, which standards are used as references and how a facility's protection needs are assessed.
An electromagnetic pulse is a very high-intensity electromagnetic field event lasting anywhere from nanoseconds to seconds. Its natural forms include lightning and solar storms. High-altitude electromagnetic pulse (HEMP) is the pulse created by a nuclear explosion in the upper atmosphere, which can affect an area of hundreds or even thousands of kilometres at once.
HEMP is described by three components. The E1 component is a very fast field that rises within a few nanoseconds and can reach tens of kilovolts per metre; it is the most dangerous part for electronic circuits. The E2 component has characteristics similar to lightning. The E3 component is a slow field lasting seconds that can damage transformers by inducing large currents, especially in long power transmission lines. This environment is defined in standards such as IEC 61000-2-9.
There are two main ways a pulse reaches a system. The first is direct radiation: the field passes through the walls and windows of the building and reaches the equipment inside. Reinforced concrete buildings partly weaken this field, but not enough to protect electronic equipment. The second, and often more dangerous, is the pulse arriving by conduction.
Long power, communication and signal cables collect the pulse field like antennas, convert it into very high currents and voltages and carry these straight to the inputs of equipment inside the building. That is why the weakest point of a facility is often not its walls but the cables coming in from outside. Effective protection must address both paths together.
The basis of EMP protection is placing the systems to be protected inside an electromagnetically closed volume. This volume is usually a shielded room made of welded or modular steel panels. The walls, ceiling, floor, doors and ventilation openings of the room must form a continuous shield that keeps the pulse from getting in.
Every line entering the room is a potential opening that breaks the continuity of the shield. Power lines are protected with pulse-rated filters and surge protectors, data lines with fibre optics and waveguide penetrations, and ventilation with honeycomb filters. All these entry elements are gathered on a single entry panel on the shield and kept under control.
One of the most common references for EMP protection of fixed facilities is MIL-STD-188-125-1. This standard defines in detail the shielding effectiveness of the protected volume, the performance of protectors at entry points and the verification tests. For transportable systems, part MIL-STD-188-125-2 of the same series is used. The standard is based on a shielding effectiveness target of 80 dB between 10 MHz and 1 GHz for the protected volume.
On the civil side, the parts of the IEC 61000 series dealing with HEMP and high-power electromagnetic events provide a broad framework, from defining the environment to protection design and test methods. Which standard is used depends on the nature of the facility, the customer's specification and national regulations. We explain what shielding values mean in our article what is dB.
In EMP protection, lines are not protected at a single point but in stages. Long external lines entering the building first pass through protection at the building entry point, where most of the pulse is diverted to earth. Filters and protectors on the shielded room's entry panel then reduce the remaining energy to a level the equipment inside can withstand.
This approach shares the same logic as OT security in critical infrastructure and HIRF and lightning protection in aviation. For protectors to work correctly, the earthing system must be low-impedance and well designed, and the protectors must be selected to coordinate with each other. You can find the basics of pulse testing at product level in our article on the IEC 61000-4-5 surge test.
The facilities that most need EMP protection are those whose outage would have wide-ranging consequences. Military command and control centres, emergency coordination centres, critical data centres, control systems of energy and water infrastructure and communication hubs fall into this group. The aim in these facilities is to keep core functions running even after a major electromagnetic event.
Not every facility needs the same level of protection. The level of protection is set by a risk analysis that considers together the facility's criticality, geographic location, the nature of the data it processes and the budget. In most cases, instead of the whole facility, only one or a few rooms containing the most critical systems are protected. We describe our approaches for data centres on our data centres page.
Once installation is complete, measurement must verify that the protection actually works. The shielding effectiveness of the room is measured over the specified frequency range and at defined points. The pulse withstand of filters and protectors at entry points is checked with the pulse injection tests defined in the relevant standards.
Verification is not a one-off exercise. Door gaskets wear, connections loosen and new lines are added over the years. For this reason a periodic measurement and maintenance programme is an integral part of protection design in EMP-protected facilities. You can read how shielding measurement is done in our article how is shielding effectiveness measured and find our solutions on our EMP/HEMP protected room page.
The shielding effectiveness of the room is measured at specific frequencies, and the pulse withstand of filters and protectors at entry points is verified with the pulse injection tests defined in the relevant standards.
Line protectors also protect against lightning-induced pulses. However, the building's own lightning protection system must be designed separately.
Yes. Partial protection can be provided by adding a shielded room or shielded cabinet for critical systems and protecting line entries.
HEMP is the wide-area pulse created by a nuclear explosion at high altitude. IEMI refers to more local but more likely intentional attacks carried out with portable high-power transmitters.
Usually not. The most critical systems identified by risk analysis are gathered in one or a few shielded rooms and protected.
MIL-STD-188-125-1, a common reference for fixed facilities, is based on 80 dB shielding effectiveness between 10 MHz and 1 GHz for the protected volume. The project specification may define a different target.