Data Center Shielding: The Risk Software Cannot Cover

The electromagnetic signals servers emit are a physical security gap. The role of shielding in data centers.

When data centre security comes up, most people think of firewalls, encryption and access rights. Yet every running server, display, keyboard and cable emits weak electromagnetic signals related to the data it processes. With the right equipment these signals can be picked up from outside the building, or even from an adjoining room, and no software security measure can stop this physical leakage.

Public institutions, defence companies and financial organisations that process classified data close this risk with electromagnetic shielding. In this article we explain what shielding in data centres protects against, how practical challenges such as cooling and cabling are solved, and when protection should be done at room scale and when at cabinet scale.

What Is Physical Leakage?

In electronic devices, signals are carried by currents that are constantly switching on and off, and these currents inevitably radiate electromagnetic energy into their surroundings. Part of this radiation is directly related to the data being processed. These signals from sources such as display cables, keyboard lines and server buses can be turned back into meaningful information with the right receiver and processing methods. Such leakage and the measures taken against it are covered under the heading TEMPEST.

Leakage is not limited to signals radiated through the air. Every conductor leaving the building, such as power cables, earthing lines, telephone and network cables, can carry the signals inside out by conduction. That is why effective protection has to address both the field radiated through the walls and every line leaving the room. We explain the fundamentals in our article what is TEMPEST.

What Does Shielding Protect Against?

A shielded data room protects against three different risks. The first is the unintended information leakage described above. The second is attacks aimed at disrupting systems with strong electromagnetic signals sent deliberately from outside. The third is the damage that high-energy events such as lightning or electromagnetic pulses can do to electronic equipment.

Not all of these risks require the same level of protection. For protection against information leakage, it is enough for the room to provide high shielding effectiveness over a certain frequency range and for all lines to be filtered, while pulse protection additionally requires surge-rated protectors at line entries. Which threat comes first is decided by the nature of the data the facility processes and by a risk assessment.

Cooling and Ventilation

The biggest need of data rooms is cooling, and in a shielded room every air passage is a potential leakage point. This problem is solved with honeycomb ventilation filters. The cells of a honeycomb filter are designed narrow and long enough that electromagnetic waves below a certain frequency cannot pass; air passes freely while the signal does not. We explain the working principle in detail in our article on the honeycomb ventilation filter.

Honeycomb filters add some resistance to airflow. Cooling capacity and duct cross-sections should therefore be set at the design stage taking filter losses into account. Air conditioning indoor units are placed inside the room where possible, and only the refrigerant pipes or water lines enter the room through special penetrations. Compared to large air duct penetrations, this approach is both safer and more efficient.

Cabling: Fibre, Filters and Penetrations

In a shielded data room, the safest solution for data lines is fibre optics. Fibre cable does not conduct electricity, so it carries no leakage, and it can be brought into the room through narrow metal tubes that work on the waveguide principle. Copper network cables, on the other hand, should not leave the room directly; where this is unavoidable they must pass through suitable filters.

For power lines, power line filters with suitable current and leakage current ratings are used on every phase and neutral line. When selecting filters, UPS output characteristics, compatibility with residual current devices and future load growth should be evaluated together. We cover this topic in our article on power line filter selection.

  • Data connections: fibre optics and waveguide penetrations wherever possible
  • Power: a suitable power line filter for every line
  • Ventilation: honeycomb filters
  • Earthing: a controlled, single-point connection

Room or Cabinet?

Shielding an entire data centre is usually neither necessary nor economical. Typically, servers processing classified data or critical systems are placed inside a separate shielded room. This approach reduces the volume that needs protection and does not affect the normal operation of the rest of the data centre.

When only a few critical servers are involved, shielded rack cabinets offer an even more economical solution. These cabinets form a shielded volume on their own with their own filtered power input, honeycomb ventilation and fibre penetrations. However, because heat density inside the cabinet will be high, cooling capacity must be calculated carefully, and the time the door stays open during maintenance should be included in security procedures.

New Build or Conversion?

Shielding gives the most efficient result when the data centre is newly built or undergoing a major refurbishment. At this stage, room dimensions, cable routes, cooling infrastructure and the raised floor can be designed together with the shielding. In an operating data centre, modular room-in-room solutions are usually preferred to minimise downtime.

The first step in converting an existing space is a site survey and measurement. The building structure, existing cable routes, floor load capacity and cooling infrastructure are examined to determine which solution can be applied. We share our experience with converting office spaces in our article on converting an existing office into a shielded room.

A Layered Security Approach

In a data centre, shielding is not a measure on its own but one layer of an electromagnetic security approach. Real security is achieved when shielding against information leakage, monitoring against intentional interference and line protection against pulses are planned together. Physical access control, camera systems and staff procedures are complementary parts of this structure.

Periodic measurement and maintenance are essential for shielding to remain effective over time. Door gaskets, filter connections and cable penetrations added later can reduce shielding performance over the years. You can read about this layered approach in our article on EMSEC in the data centre, and about our implementation options on our data centres page.

Frequently Asked Questions

Should the whole data centre be shielded?

Usually not. Areas processing classified data or critical systems are placed in a separate shielded room or shielded cabinet, and the rest of the space continues to operate normally.

Does shielding make server maintenance harder?

With properly planned doors, cable penetrations and ventilation, maintenance is carried out normally. Only the time the door stays open should be defined in security procedures.

When is a shielded cabinet enough?

When only a few critical servers need protection, it is an economical solution at single-rack scale. Because heat density will be high, cooling capacity must be calculated carefully.

Can copper network cable be used in a shielded room?

It can be used inside the room, but fibre optics should be preferred for data connections leaving the room. If copper lines must leave the room, they need to pass through suitable filters.

Does shielding effectiveness decrease over time?

Worn door gaskets, loosened connections and penetrations opened later can reduce performance. Periodic measurement and maintenance are therefore recommended.

What shielding value should a shielded data room target?

In security rooms the target is generally set between 80 and 100 dB. The exact value and measurement frequency range are defined by the organisation's security specification and the classification level of the protected data.