How to Write a Shielded Room Specification
Which values a shielded room specification for a tender or purchase must state, and the common mistakes to avoid, explained point by point.
A point-by-point list of what to check in advance in the area where a shielded room will be installed: floor, ceiling, power, ventilation and access.
A significant part of the delays and extra costs in shielded room projects comes not from the room itself but from the building where it will be installed. Materials that do not fit in the lift, a floor that cannot carry the load, an unexpected beam in the ceiling or a main power line running right next to the room can extend the installation schedule by weeks.
In this article we have collected, as a checklist, the items to check in the building before installing a shielded room. From floor and load capacity to ceiling height, from the access route to power, ventilation and communication infrastructure, and from nearby signal sources to fire safety, we explain why each item matters and how to prepare.
Shielded rooms add a significant weight per square metre depending on the panel type used. In anechoic chambers, absorbers, a turntable and heavy equipment to be tested increase this load noticeably. In rooms using ferrite tiles, the weight of the absorbers alone can be a serious load. The load capacity of the floor should therefore be checked by a structural engineer before installation.
The flatness of the floor is as important as its load capacity. When shielded room panels are installed on a flat floor, joints seat better and the door is easier to adjust. On noticeably sloping or uneven floors, a levelling screed or an adjustable substructure may be needed. The room floor is also installed with an insulating layer to isolate it electrically from the building concrete; the thickness of this layer must be included in the ceiling height calculation.
The internal height of a shielded room is noticeably less than the clear ceiling height in the building. Space must be left above the room ceiling for installation and maintenance, and the floor insulation layer, panel thicknesses and any absorbers reduce the internal height. Beams, sprinkler pipes, cable trays and ventilation ducts can also limit usable height. For this reason not only the ceiling height but all obstacles at ceiling level should be measured during the survey.
How materials will reach the building and the installation area should also be planned in advance. Corridor widths, door sizes and lift capacity should be checked for the panels, door frame, turntable and absorber boxes. In some projects materials may need to be lifted in by crane through the facade, or a temporary opening may need to be made. The earlier this need is known, the smaller its cost and schedule impact.
Every power line entering the shielded room passes through a power line filter. A distribution board and supply of suitable capacity near the room are needed to feed these filters. Cable sizes and breaker ratings should be set taking into account the total power of the equipment to be used in the room, lighting, air conditioning and future load growth.
By their nature, power line filters leak current to the earth line. This can cause residual current devices to trip unintentionally. The protection arrangement on the room's supply must therefore be designed taking into account the filter manufacturer's recommendations and the relevant electrical regulations. We explain filter selection in detail in our article on power line filter selection.
The air-conditioning needs of a shielded room are calculated according to the number of people working inside and the heat generated by equipment. Air is supplied and extracted through honeycomb-filtered penetrations. These penetrations should be planned close to the building's existing duct system, at a point where the duct connection can be made easily. The location of the air-conditioning outdoor unit and the connecting pipes should also be decided at this stage.
For communications infrastructure, the number and type of data connections entering the room should be determined in advance. Data connections are usually made with fibre optics, with fibre converters inside the room. The cables of systems such as telephone, cameras, card access and fire detection must also enter the room through filtered penetrations. Adding these needs later requires the shielding to be reopened and re-verified.
When choosing the room's location, strong electromagnetic sources nearby should be considered. Transformer rooms, main distribution boards, lift machine rooms and base stations on the roof can increase the shielding level the room will need. Low-frequency magnetic fields in particular cannot be fully blocked by standard shielded room panels and can cause problems in rooms where precision measurements are made.
Ambient measurements at candidate locations during the survey are therefore recommended. As a result of the measurement, sometimes moving the room just a few metres can significantly reduce the required shielding level and cost. For transformer-related magnetic fields and their solutions, see our article on magnetic shielding.
A shielded room should be thought of as part of the building's fire safety system. There should be a fire detection system inside the room, and its signals should be transmitted to the building's central system through filtered penetrations. If a sprinkler or gas suppression system is needed, suitable shielded penetrations should be planned for the pipes to enter the room.
The room door must always be openable from the inside in an emergency, and escape routes must comply with regulations. The fire behaviour of the absorber and lining materials used should also be evaluated. Addressing these topics before installation with the building's fire consultant and the competent authorities prevents later changes. We explain the details in our article on fire detection in shielded rooms.
Shielded room installation should be coordinated with other work in the building. Dust, moisture and heavy construction activity can affect the quality of panel joints and gaskets. For this reason, shielded room installation usually starts after the shell construction and dusty work are complete. During installation it is important for the area to be lockable and controlled to protect the materials.
A detailed work schedule prepared before installation should include material delivery, assembly, electrical and air-conditioning connections, interior fit-out and the acceptance measurement. If welding, cutting or heavy electrical work needs to be done near the room during installation, its timing should be planned in advance. Contact us for a free site survey; during the survey we go through this whole checklist together.
Yes. Floor load capacity is usually better; however, humidity, ventilation and the material access route should be assessed in advance.
Yes, but dusty work, welding and cutting in nearby areas should be coordinated with the installation schedule.
It is possible, but a gap between the walls and the room is usually recommended for maintenance and measurement access.
Space must be left above the room ceiling for installation, maintenance and penetrations. The exact value is determined in the survey according to room type and ceiling obstacles.
The leakage current of power line filters can trip standard residual current devices. The protection arrangement should be designed taking filter characteristics and regulations into account.
It is recommended for locations near transformers, lifts or base stations. The measurement helps determine the room's location and the required shielding level.