Anechoic Chambers

How to Size an Anechoic Chamber: From Test Distance to Building

The factors that set an anechoic chamber's internal and external size, such as test distance, product size, absorber depth and service space, step by step.

The first question from organisations planning an anechoic EMC chamber is usually how much space the chamber will take up. The answer depends not only on the test distance but also on the size of the products to be tested, the thickness of the absorbers to be used, the height of the antenna mast and the auxiliary areas needed around the chamber. A wrong estimate means either a chamber that does not fit in the building or a small chamber that does not meet the need.

In this article we explain step by step how anechoic chamber size is calculated, starting from the test distance. We look at how product and test volume, absorber thickness, height and additional space in the building are taken into account, the typical dimensions of different chamber types and how chamber size affects cost.

The Starting Point: Test Distance

The first factor determining the size of an anechoic chamber is the distance between the measurement antenna and the product under test. The most common test distances in EMC standards are 3 m, 5 m and 10 m. This distance is usually measured not from the centre of the product but from the product's boundary or the edge of the test volume. The test distance is the main component of the chamber's length.

Which test distance is chosen depends on the standards to be applied and the size of the products to be tested. For small electronic products, 3 m is usually enough, and measurements at this distance are assessed with limits corrected for distance. For large products, some certification requirements and the highest measurement accuracy, 10 m is preferred. 5 m offers an intermediate solution between the two.

Product and Test Volume

The test volume is the cylindrical space the product under test and its cables occupy on the turntable. Its diameter is set by the largest product to be tested. Because the test distance is usually measured from the edge of the test volume, the radius of the test volume is added to the chamber's length. A certain clearance must also be left behind the product up to the absorbers.

The chamber's width is also set by the test volume and the antenna's radiation pattern. Enough distance must be left beside the test volume and antenna that reflections from the side walls do not affect the measurement. These distances are critical for the chamber to pass its NSA and SVSWR validations.

  • Test distance: between antenna and edge of test volume
  • Test volume: largest product and its cables
  • Clearances behind the product and behind the antenna
  • Distances to the side walls

Absorber Thickness

Absorbers line the chamber's inner surfaces, and their thickness directly reduces the inner volume. Ferrite tiles are only a few millimetres thick and affect inner volume very little. Hybrid absorbers consist of foam absorbers placed in front of ferrite tiles and are usually tens of centimetres thick. In chambers lined only with pyramid absorbers, absorbers can be metres long for good performance at low frequencies.

So for the same test distance, the chamber's outer dimensions can change significantly depending on absorber type. Hybrid absorbers, usually preferred in EMC chambers, strike a balance between good low-frequency performance and reasonable thickness. We explain the characteristics of hybrid absorbers and other absorber types in detail in our related article.

Height

The height of a semi-anechoic chamber is set by the antenna mast's range of movement. In standard measurements the antenna is moved between 1 m and 4 m; the chamber's inner height must therefore leave enough clearance above the antenna at 4 m up to the ceiling absorbers. If large products are to be tested, the product's height and the clearance above it are also taken into account.

The chamber's outer height is set by the inner height, the thickness of the ceiling absorbers, the chamber structure and the maintenance and penetration clearance above the chamber. A pit in the floor is also needed for a flush-mounted turntable. Height is the constraint most often met in existing buildings; many buildings do not have enough ceiling height even for a standard 3 m chamber.

Typical Dimensions

Although exact dimensions vary with absorber type and design, a general idea of typical chamber dimensions can be given. Chambers with a 3 m test distance usually have an inner length of about 8 to 10 m, a width of 5 to 7 m and a height of 5 to 6 m. Chambers with a 10 m test distance are much larger, with inner lengths of 18 to 22 m and heights of 8 to 10 m.

These dimensions refer only to the chamber's inner volume. Outer dimensions, with the panel structure, absorbers and maintenance clearances around the chamber, are larger. So the space that must be allocated in the building for a chamber is noticeably more than its inner dimensions. These estimates offer a starting point; exact dimensions are set by a design based on a needs analysis.

Building and Additional Areas

An EMC laboratory does not consist only of the test chamber. A control room, amplifier room, product preparation area, equipment storage and staff areas are needed next to it. The positions of these areas relative to the test chamber directly affect the laboratory's efficiency. We discuss this in detail in our article on control room design.

Access clearances for installation, maintenance and measurement must also be left around the chamber. Wide doors, suitable corridors and, if necessary, crane access must be planned for moving heavy products. Adapting an existing building can be difficult for large chambers; in that case a separate structure for the chamber or conversion of an existing industrial building can be considered.

Chamber Size and Cost

Chamber size is one of the most important factors directly affecting cost. As the chamber gets bigger, panel, absorber, labour and air-conditioning costs rise. Absorber cost in particular rises in proportion to the surface area to be covered. Large chambers also require larger turntables, more powerful amplifiers and larger building investments.

Setting chamber size according to real need therefore optimises both the initial investment and operating costs. A chamber larger than needed means unnecessary cost, while one smaller than needed cannot meet the need and is very expensive to enlarge later. For our chamber options, see the SAC-3, SAC-5 or SAC-10 types, and for compact solutions our SAC-3 page.

Frequently Asked Questions

Roughly how much space does a 3 m chamber need?

Inner dimensions are usually 8–10 m long, 5–7 m wide and 5–6 m high. The space to be allocated in the building is larger, with maintenance clearances and additional areas.

What happens if ceiling height is insufficient?

The antenna height scan range may be restricted, affecting the measurements' compliance with the standard. A different location or structure should then be considered.

How does chamber size affect price?

As the chamber grows, panel, absorber, labour, air-conditioning and building costs rise. Setting size according to real need optimises cost.

What is the difference between a 3 m and 10 m chamber?

A 10 m chamber allows larger products to be measured more accurately and is preferred for some requirements, but needs much more space and investment.

Does absorber type affect chamber size?

Yes. Ferrite and hybrid absorbers reduce the inner volume little, while long pyramid absorbers require a larger chamber for the same test distance.

Can the chamber be enlarged later?

It is possible with modular structures but costly because of absorbers, turntable and building conditions. Setting the size correctly from the start is recommended.